Siemens G120 A01028 Fault - Causes & Fix

3 min read
⚡ Quick Answer

A01028 means the drive's saved configuration was made for a different module type. Save parameters with p0971=1 or reload the correct project.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Siemens G120 A01028 Fault — What It Means

Fault code A01028 on a Siemens SINAMICS G120 is a configuration error alarm. It appears when the drive detects that the downloaded parameter set was created for a different hardware module than the one physically installed. The drive compares the stored configuration’s target module type and order number (MLFB) against the actual Control Unit and Power Module present, and this alarm triggers when they do not match. The alarm reaction is NONE and it requires no acknowledgment, but it signals that your commissioning data is inconsistent with the installed hardware. This is not an electrical failure but a mismatch between the project file and the drive identity.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Check the installed drive nameplate for the exact order number (MLFB) and module type, and write down the Control Unit and Power Module part numbers from the physical G120 unit.
  2. Open your commissioning project in Startdrive or the Siemens tool you used, navigate to the device configuration, and verify that the selected Control Unit and Power Module types match the installed hardware exactly.
  3. Save parameters non-volatilely by setting parameter p0971 to 1 and executing the command, which writes the current configuration to the drive’s permanent memory.
  4. Power-cycle the drive completely by removing control power for at least 10 seconds, then restore power so the drive reloads the saved configuration from non-volatile memory.
  5. Verify the alarm clears by checking the drive display or diagnostic buffer, and confirm that the module type in the drive properties now matches the installed hardware.
  6. Reload the correct project if the alarm persists: create or download a new project in Startdrive for the exact MLFB of your installed G120 module, then download it to the drive and save with p0971=1.
  7. Inspect for Control Unit or memory faults if a known-correct project still triggers A01028 after a full power cycle, as the module identity circuitry or stored calibration data may be corrupted and require hardware service.

Parts Often Needed

PartNotes
Siemens G120 Control Unit (CU) matching installed MLFBAmazon | Required if the current Control Unit has failed or the stored module identity cannot be corrected by reloading the project.
Siemens G120 Power Module (PM) matching installed MLFBAmazon | Needed if the Power Module was replaced without updating the project, or if the physical module does not match the commissioned configuration.
Siemens Startdrive commissioning software licenseAmazon | Used to create, edit, and download the correct parameter set for your exact G120 module variant and save it non-volatilely.

When to Call a Pro

Call a qualified Siemens drive technician or automation integrator if you cannot identify the installed module MLFB, if you do not have access to the original commissioning project or Startdrive software, or if the alarm returns after correctly matching the project to the hardware and saving with p0971=1. Also contact a professional if the drive was part of a coordinated system (PLC, motion control, or multi-axis setup) where changing parameters could affect other equipment. If the Control Unit or Power Module identity cannot be read or verified through the drive interface, the hardware may have a memory or circuit fault that requires factory-trained service and possible module replacement under warranty.