Siemens G120 F30002 - Causes & Fix

3 min read
⚡ Quick Answer

Siemens G120 F30002 is a DC-link overvoltage fault. Learn the causes, diagnostic steps, and repair procedure for this drive fault.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Siemens G120 F30002 — What It Means

F30002 on a Siemens SINAMICS G120 means DC-link overvoltage. The power unit has detected that the intermediate circuit voltage has exceeded its permitted limit and trips to protect itself. This is a drive hardware protection fault, not a motor overload condition.

The fault is most often associated with regenerative energy returning from the motor back into the DC link, especially during deceleration or braking. When energy flows back faster than the drive can absorb or dissipate it, the DC bus voltage rises above the safe threshold and triggers the fault.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Stop the drive safely and verify there is no mechanical runaway or hazardous motion from the load.
  2. Identify when the fault occurs by checking whether it trips during deceleration, stopping, lowering a load, or speed changes to narrow down the root cause.
  3. Inspect the braking resistor and wiring to confirm it is present, correctly connected, not open circuit, and shows no signs of overheating or damage.
  4. Review and lengthen the deceleration ramp time in the drive parameters to reduce the regenerative energy peak and allow more time for the drive to absorb it.
  5. Check the supply voltage quality using a multimeter or power analyzer to confirm the incoming mains are stable and within specification.
  6. Review the drive’s diagnostic buffer using the control panel or STARTER software to confirm the DC-link voltage reading at the time of fault.
  7. Test-run the drive after making changes and monitor the DC-link voltage during braking or load changes to verify the fault does not recur.

Parts Often Needed

PartNotes
Braking resistor for Siemens G120Amazon | Verify correct ohm and watt rating for your G120 frame size and application inertia. Consult the G120 manual for your model.
Brake chopper module (if external)Amazon | Required if your drive setup uses an external braking chopper and it has failed or is not engaging.
G120 power unitAmazon | Only replace if internal diagnostics confirm a hardware fault in the DC-link circuit itself rather than an external braking or supply issue.

When to Call a Pro

Call a qualified drives technician or Siemens service partner if you have checked the braking resistor and ramp settings but the fault persists, or if you are unfamiliar with drive parameter configuration and DC-link diagnostics. Also call a professional if the fault occurs with no apparent regenerative condition (such as during constant speed) or if the drive’s diagnostic buffer shows unusual voltage levels that suggest internal power unit damage. Applications with complex braking requirements or safety-rated motion control should always be serviced by trained personnel.