Siemens G120 F01040 - Causes & Fix

2 min read
⚡ Quick Answer

Siemens G120 F01040 is an internal software or parameterization fault. Learn how to clear it with a power cycle and parameter save.

Siemens G120 F01040 — What It Means

F01040 is a fault code on the Siemens SINAMICS G120 drive that trips the unit and requires a full power cycle after saving parameters. The drive reports an internal software or parameterization error in the Control Unit. Siemens manuals describe the remedy as saving your parameter settings and performing a POWER ON restart. This class of fault relates to inconsistent or corrupted data on the drive’s non-volatile memory or to internal software problems that prevent normal operation. Unlike an alarm, F01040 stops the drive completely until you clear the fault and address the underlying cause.

Jump to Fix

Common Causes

Step-by-Step Fix {#fix}

  1. Record the fault buffer by connecting via Startdrive or the BOP-2 panel and reading the fault history to confirm F01040 and note the time and context of the trip.
  2. Save the current parameter set to the drive’s non-volatile memory or to an external memory card if communication is still available.
  3. Perform a complete POWER ON cycle by switching off mains power to the drive, waiting at least 10 seconds, then switching it back on (do not simply press the fault-acknowledge button).
  4. Check the fault buffer again after restart. If F01040 does not return, restore normal operation and monitor for recurrence.
  5. Inspect the memory card and non-volatile storage for corruption or mismatched configuration files if the fault reappears. Replace or reformat the card and reload a known-good parameter set.
  6. Update the firmware to the latest approved version for your G120 model if Siemens support notes or service bulletins document a fix for internal software faults.
  7. Replace the Control Unit if F01040 persists after power cycling, memory verification, and firmware update. Transfer your saved parameter set to the new CU and commission the drive.

Parts Often Needed

PartNotes
Siemens SINAMICS G120 Control Unit (CU)Amazon | Required if the fault persists after power cycling, memory checks, and firmware update. Match the CU model to your Power Module.
Siemens SINAMICS memory cardAmazon | Replace if the installed card shows corruption or read/write errors. Format and load a verified parameter set before installation.

When to Call a Pro

Call a qualified drives technician or Siemens service partner if F01040 returns after you have saved parameters, performed a full power cycle, and verified the memory card. If you are not familiar with Startdrive software, fault-buffer diagnostics, or firmware update procedures, get professional help before replacing the Control Unit. Persistent internal software faults can indicate deeper hardware problems that require bench testing and factory repair. Always contact support if the drive is under warranty or if your process cannot tolerate trial replacements.


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.
Get Free Quotes →