Siemens G120 F01034 - Causes & Fix

2 min read
⚡ Quick Answer

F01034 on Siemens G120 means parameter reference value change failed. Learn causes, diagnostic steps, and when to replace the Control Unit.

Siemens G120 F01034 — What It Means

F01034 on a Siemens SINAMICS G120 indicates that the drive accepted a parameter change to a reference value, but one or more related parameters could not be recalculated correctly in per-unit format. The drive responds by rejecting the change and restoring the original parameter value. This is a parameterization or engineering fault, not an overcurrent, ground fault, or power-stage failure.

The fault triggers when a reference parameter tied to the drive’s internal scaling is changed to an incompatible value that cannot be converted cleanly in the per-unit system. The drive’s internal calculations depend on consistent reference values across linked parameters, and when a new value breaks that consistency, the conversion fails and the fault is raised.

Jump to Fix

Common Causes

Step-by-Step Fix {#fix}

  1. Identify the last parameter changed before the fault appeared by reviewing the parameter change log in Startdrive or the drive display, and note the previous working value.
  2. Review all related reference and scaling parameters in the same parameter group to verify consistency, since the fault is triggered by a change in one reference parameter affecting linked values.
  3. Restore the original parameter value or enter a new value that remains within the valid conversion range for the affected drive object, using the drive’s parameter documentation for acceptable limits.
  4. Acknowledge and reset the fault using the control panel or Startdrive after correcting the parameter condition.
  5. Re-download the commissioning data set or manually re-enter the parameter set carefully if the fault repeats, focusing on reference and scaling parameters.
  6. Test the drive by running a controlled ramp to verify the parameter change is accepted and no fault recurs.
  7. Replace the Control Unit if the drive continues to reject valid parameter values and the fault persists after re-commissioning.

Parts Often Needed

PartNotes
Siemens G120 Control Unit (CU)Amazon | Required only if the fault persists after correcting parameters and re-commissioning, indicating an internal calculation failure.

When to Call a Pro

Call a qualified Siemens drive technician if you are not familiar with Startdrive or SINAMICS parameter structures, or if the fault repeats after you have restored original reference values and re-downloaded a known-good parameter set. If the Control Unit replacement is indicated and you do not have experience with G120 commissioning and parameter backup, professional service will prevent data loss and configuration errors during the swap.