Skip to content
Industrial Error Code Fixes
Go back

Siemens G120 A03520 - Causes & Fix

2 min read
⚡ Quick Answer

Siemens G120 alarm A03520 signals a temperature sensor fault in the Control Unit. Learn causes, diagnostics, and repair steps.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Siemens G120 A03520 — What It Means

A03520 is an alarm (not a trip fault) on the Siemens SINAMICS G120 that indicates a temperature sensor error in the Control Unit (CU). The drive has detected a problem with the CU’s internal temperature-sensing circuit, not a motor overload or power-module issue. The alarm is stored in the drive’s diagnostic memory and appears as “CU: Temperature sensor fault” or “Temperature Sensor Error” in the fault text.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Read the active alarm in the drive diagnostics and confirm code A03520 is stored in parameter r2110 (active alarms) or the fault history in r0947, r0948, or r0949.
  2. Perform a complete power-off, power-on cycle of the drive and associated components to clear any temporary corruption, as recommended in Siemens remedy documentation.
  3. Inspect the Control Unit for signs of overheating, discoloration, contamination, or visible damage to connectors and circuit board components.
  4. Check any accessible CU temperature-sensor harness or plug for looseness, corrosion, or physical damage if your hardware version has an external sensor path.
  5. Replace the Control Unit if the alarm returns immediately after power cycling and no external wiring faults are found.
  6. Verify the new CU by powering up and monitoring r2110 to confirm A03520 does not reappear.
  7. Escalate to manufacturer-level service if the alarm persists after CU replacement, as the fault is in the temperature-sensing circuit rather than the power module.

Parts Often Needed

PartNotes
Siemens SINAMICS G120 Control Unit (CU)Amazon | Match the exact CU variant (CU240, CU250, etc.) to your G120 order number or MLFB label.
CU temperature sensor harness or connectorAmazon | Only if your hardware version uses an accessible external sensor path. Consult your drive documentation.

When to Call a Pro

Call a qualified Siemens service technician or automation specialist if the alarm persists after a full power cycle and you are not comfortable replacing the Control Unit yourself. If the alarm returns immediately after installing a new CU, or if you are unsure which CU variant matches your drive model, professional diagnosis is required. Escalate to the manufacturer if the fault is intermittent or accompanied by other drive errors, as it may indicate a deeper electronics or environmental issue.

See Also


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.
Get Free Quotes →
Share this post on:

Previous Post
Siemens G120 A05000 - Causes & Fix
Next Post
Siemens G120 F03505 - Causes & Fix