Siemens G120 A01028 - Causes & Fix

3 min read
⚡ Quick Answer

Siemens G120 A01028 is a configuration error alarm caused by parameter and hardware mismatch. Learn causes, diagnostic steps, and parts.

Siemens G120 A01028 — What It Means

The A01028 alarm on a Siemens SINAMICS G120 is a configuration error, not a hardware trip fault. Siemens describes it as a parameterization mismatch where the downloaded settings were generated for a different module type or order number (MLFB) than the one physically installed in the drive. The alarm text reads: “The loaded settings are not compatible with the inverter.” This means the drive’s actual hardware does not match the stored configuration, typically because the wrong device type was selected in the project or parameters were restored from another drive with a different MLFB. The alarm does not indicate a direct hardware failure but rather a commissioning or configuration error that prevents the drive from accepting the parameter set.

Jump to Fix

Common Causes

Step-by-Step Fix {#fix}

  1. Verify the exact drive nameplate and MLFB numbers on both the Control Unit and Power Module, then compare them to the hardware configuration in your TIA Portal or Startdrive project to confirm they match.
  2. Check the drive’s alarm buffer and diagnostics to confirm A01028 is the active issue and that no separate hardware faults are present that could complicate troubleshooting.
  3. Correct the project hardware configuration in TIA Portal or Startdrive to match the installed drive hardware, then download the corrected parameter set to the drive.
  4. Save parameters non-volatilely by setting parameter p0971 to 1, which Siemens specifically recommends to clear the alarm after correcting the mismatch.
  5. Power cycle the drive by switching off mains power, waiting 30 seconds, and powering back on to allow the drive to reload the corrected configuration.
  6. Re-commission the drive if the alarm returns after correction, following Siemens’ recommended startup procedure for your specific G120 model rather than forcing the old parameter set.
  7. Replace the Control Unit or inverter only if the alarm persists after verifying correct hardware configuration and re-commissioning, as this indicates a hardware issue preventing parameter acceptance.

Parts Often Needed

PartNotes
Siemens G120 Control Unit (CU)Amazon | Match the exact MLFB to your Power Module. Replace if re-commissioning does not clear the alarm after correct configuration.
Siemens G120 Power Module (PM)Amazon | Verify the MLFB matches your Control Unit and project configuration. Required if the installed module type is incompatible with your system.

When to Call a Pro

Call a qualified technician or Siemens service partner if you do not have access to TIA Portal or Startdrive to verify and correct the hardware configuration in your project. Also reach out if the alarm persists after you have confirmed matching MLFB numbers, re-commissioned the drive, and power cycled it. Configuration errors can sometimes mask deeper issues with Control Unit memory or firmware compatibility that require specialized diagnostic tools and factory support. If you are unsure how to safely power down the drive or lack training on Siemens parameter management, professional assistance will prevent accidental data loss or further configuration problems.