SEW MOVIDRIVE Fault Codes: F08, F42, F07 and Full List

⚡ Quick Answer

SEW MOVIDRIVE MDX60B/61B fault code list from the SEW system manual: F08 speed monitoring, F42 lag fault, F07 overvoltage, F01 overcurrent, F14 encoder, F25 EEPROM, with causes and fixes.

⚡ AT A GLANCEScroll down for full repair guide
What it meansMOVIDRIVE MDX60B/61B shows a flashing F plus a two or three digit code on the 7-segment display. F08 is speed monitoring, F42 is a positioning lag fault, F07 is DC link overvoltage, F01 is overcurrent, F14 is an encoder fault.
Most likely causeMost F08 trips come from a drive running at its current or slip limit (overload, phase failure) or an encoder wired backwards; F42 comes from ramps that are too short, a P gain that is too low, or a lag window that is too tight.
First checkRead the subfault code in MOVITOOLS MotionStudio or on the DBG60B keypad, then check load, encoder wiring and direction, ramp times and the P50x monitoring or P9xx positioning parameters before swapping hardware.
⏱Repair time10-30 minutes for parameter, ramp and encoder-wiring checks; 1-3 hours for braking resistor, encoder, option card or memory card replacement
🔧Part neededSEW braking resistor, encoder cable and sine/cosine or Hiperface encoder, DEH11B/DER11B encoder option card, memory card, DBG60B keypad

Parts to price first

Check the part before you book service.

SEW MOVIDRIVE braking resistor

For F04 brake chopper and F07 DC link overvoltage trips; match resistance and wattage to the MDX size.

$90-$400Check price

SEW DBG60B keypad

Shows the subfault code and plain-text fault name instead of the flashing 7-segment digits.

$150-$450Check price

Encoder cable for SEW DEH11B / DER11B option

Shielded, prefabricated encoder cable for F14, F57, F58 and F59 encoder faults.

$60-$250Check price

USB11A / RS485 programming interface for MOVITOOLS

Needed to read subfault codes, fault history and set P501/P503 or P9xx parameters from a PC.

$120-$350Check price

Equipment service manual download (eManualOnline)

The full OEM-style workshop manual has the wiring diagram, test values, and the fault table this guide summarizes. Instant PDF download.

Repair intent

Need this fixed instead of diagnosed?

SEW MOVIDRIVE MDX60B/61B fault code list from the SEW system manual: F08 speed monitoring, F42 lag fault, F07 overvoltage, F01 overcurrent, F14 encoder, F25 EEPROM, with causes and fixes.

SEW MOVIDRIVE Fault Codes: How the Display Works

SEW MOVIDRIVE MDX60B and MDX61B drives report faults on the front 7-segment display as a flashing F followed by the digits of the code, one at a time. The system manual (SEW publication 27793230, edition 08/2022) describes the sequence: flashing for about 1 second, display off 0.2 seconds, hundreds digit if any, tens, then ones, each for about 1 second with 0.2 second gaps. So F08 shows as F, blank, 0, blank, 8, then repeats. After a reset, or if the fault code returns to 0, the display switches back to the operating display.

Each fault also carries a subfault code that pins down the exact trigger. SEW states that the subfault is displayed only in MOVITOOLS MotionStudio or on the DBG60B keypad, so plug in before you start swapping parts. The “Response” column in the tables below is the factory setting; (P) means you can change the response through the P83x fault response parameters.

Jump to F08 | Jump to F42

MOVIDRIVE Fault Code Table

Wording in the Designation column follows the SEW system manual, section 16.3 Fault list. Subfault numbers are given where they change the diagnosis.

CodeDesignationResponseLikely causeFix
F01OvercurrentImmediate stopOutput short circuit, motor too large, defective output stage, ramp too short with ramp limit offRectify the short, fit a smaller motor, activate P138 or extend the ramp; SEW Service if the output stage is defective
F03Ground faultImmediate stopGround fault in motor lead, inverter or motorEliminate the ground fault; consult SEW Service
F04Brake chopperImmediate stopToo much regenerative power, braking resistor circuit interrupted or shorted, resistance too high, chopper defectiveExtend deceleration ramps, check resistor cable and data, new MOVIDRIVE if the chopper is defective
F06Line phase failureImmediate stopPhase failure, inadequate line voltage quality (subfault 3 line voltage failure, 4 line frequency fault)Check supply cable, system configuration, fuses and contactor
F07DC link overvoltageImmediate stopDC link voltage too high in 2Q (sub 0, 1) or 4Q operation (sub 2 to 4 by phase)Extend deceleration ramps, check the braking resistor supply cable and technical data
F08Speed monitoringImmediate stop (P)Controller at current or slip limit, encoder wired wrong or reversed, nmax exceeded, output frequency limit reachedSee the F08 section below
F09StartupImmediate stopStartup missing, wrong operating mode, wrong encoder type or defective encoder cardPerform startup for the required operating mode
F10IPOS-ILLOPEmergency stopInvalid IPOSplus commandCheck and correct the program memory, load the correct program
F11OvertemperatureEmergency stop (P)Thermal overload of the inverter, faulty phase module temperature sensor on size 7Reduce load or improve cooling, check the fan, replace the phase module if the temperature is not actually high
F13Control signal sourceImmediate stopControl signal source not defined or defined incorrectlySet the correct source in P101
F14EncoderImmediate stopEncoder or cable not connected or defective, shield wrong, short or broken wire, Hiperface or resolver plausibility (sub 25 to 34)Check the encoder cable and shield for connection, short circuit and broken wire
F17 to F24System faultImmediate stopElectronics disrupted, possibly EMC (stack overflow, NMI, undefined opcode, illegal access)Check and improve grounding and shielding; SEW Service if it recurs
F25EEPROMRapid stopPower section EEPROM or memory card access failed (sub 11 NV-RAM read, 13 and 14 memory card defective)Restore factory settings, reset, re-parameterize; replace the memory card
F26External terminalEmergency stop (P)External fault signal on a programmable inputEliminate the cause; reprogram the terminal if needed
F27No limit switchesEmergency stopWire break or both switches missing, switches swapped relative to rotationCheck wiring, swap connections, reprogram terminals
F28Fieldbus timeoutRapid stop (P)No master to slave communication within the monitoring timeCheck the master routine, extend P819 or deactivate monitoring
F29Limit switch hitEmergency stopHardware limit switch hit in IPOSplus modeCheck the travel range, correct the program
F30Emergency stop timeoutImmediate stopDrive overloaded, emergency stop ramp too shortCheck project planning, extend the emergency stop ramp
F31TF/TH triggerNo response (P)Motor too hot, TF/TH not connected or wired wrongLet the motor cool, then reset; check TF/TH wiring, jumper X10:1 to X10:2 if no sensor; set P835
F32IPOS index overflowEmergency stopProgramming rules violated, internal stack overflowCheck and correct the IPOSplus user program
F33Setpoint sourceImmediate stopSetpoint source not defined or defined incorrectlySet the correct setpoint source in P100
F34Ramp timeoutImmediate stopDownward ramp timed out, for example from overloadExtend the downward ramps, eliminate the overload
F35Operating modeImmediate stopOperating mode not available or wrong assignment to hardware or technology functionSet P700/P701 correctly, use the technology version, check P916 and P888
F36Option missingImmediate stopOption card type not permitted, or source or mode not permitted for the cardUse the correct option card, set P100, P101, P700/P701 and encoder type
F37System watchdogImmediate stopFault while executing system softwareConsult SEW Service
F38System softwareImmediate stopSystem faultConsult SEW Service
F39Reference travelImmediate stop (P)Reference cam missing or not switching, limit switches wired wrong, reference travel type changed during travelCheck the reference cam, limit switch connection and reference travel type
F40Boot synchronizationImmediate stopTimeout at boot synchronization with an option cardInstall a new option card if the fault recurs
F41Watchdog optionImmediate stopCommunication fault between system and option software, or IPOSplus watchdog (sub 17)Consult SEW Service; for sub 17 check the IPOS program, P079 and P078
F42Lag faultImmediate stop (P)Encoder wrong, ramps too short, P component too small, lag tolerance too smallSee the F42 section below
F43RS485 timeoutRapid stop (P)Communication timeout at the RS485 interface, manual mode timeout (sub 3)Check the RS485 connection to the PC or DBG60B
F44Device utilizationImmediate stopDevice utilization I x t above 125%Decrease power output, extend ramps, use a larger inverter
F45InitializationImmediate stopPower section EEPROM not parameterized, option card not seated on the backplane busRestore factory settings, insert the option card correctly
F46System bus 2 timeoutRapid stop (P)Communication fault on system bus CAN2Check the system bus connection
F47System bus 1 timeoutRapid stop (P)Communication fault on system bus CAN1Check the system bus connection
F48Hardware DRSImmediate stopDRS11B master or distance encoder signal faultyCheck encoder signals and wiring, replace the synchronous operation card
F57TTL encoderImmediate stopAmplitude control fault (cable, shield, short, EMC) or wrong numerator/denominator valuesCheck cable and shield, replace the encoder, correct the values
F58Sine-cosine encoderImmediate stopAmplitude, track signal, initialization or numerator/denominator faultCheck cable and shield, replace the encoder, correct the values
F59Encoder communicationRapid stopTrack signal, data line, RS485 or EnDat communication fault, wrong calibration, clock or data line not connectedCheck cable and shield, replace the encoder, connect clock and data lines, restart from delivery state
F77IPOS control wordNo response (P)Invalid automatic mode set via external controlCheck the serial connection, set P916 correctly
F78IPOS SW limit switchNo response (P)Target position outside the software limit switchesCheck the user program and limit switch positions
F79Hardware configurationImmediate stopHardware no longer matches after a memory card swapUse identical hardware or restore delivery state
F80RAM testImmediate stopInternal device fault, RAM defectiveConsult SEW Service
F81Start conditionImmediate stopVFC hoist: motor could not be magnetized correctly during pre-magnetizingCheck startup data, motor connection and cable cross section
F82Open outputImmediate stopVFC hoist: two or all output phases interrupted, nominal motor power too smallCheck the inverter to motor connection and startup data
F84Motor protectionEmergency stop (P)Motor utilization too high, sensor wire break or short (sub 2, 11), no thermal model (sub 3)Let the motor cool, reset, reduce load, extend ramps
F86Memory moduleImmediate stopNo memory card or card defectiveTighten the knurled screw, insert and secure or replace the card
F87Technology functionImmediate stopTechnology function activated in a standard unitDisable the technology function
F88Flying startImmediate stopVFC n-CTRL: actual speed above 6000 rpm at enableOnly enable at actual speed of 6000 rpm or below
F92DIP encoder problemFault display (P)Encoder is dirty (Stahl WCS3)Clean the encoder
F93DIP encoder faultEmergency stop (P)Absolute encoder signals a fault, cable does not meet requirementsCheck the encoder connection and cables, reduce travel speed or ramp
F94EEPROM checksumImmediate stopElectronics disrupted, EMC or defectSend the unit in for repair
F95DIP plausibility faultEmergency stop (P)No plausible absolute position could be determinedSet the correct encoder type, check IPOSplus travel parameters and speed
F97Copy faultImmediate stopMemory card cannot be written or read, transfer interruptedRepeat copying, restore delivery state with P802 and repeat
F98CRC faultImmediate stopInternal flash memory defectiveSend the unit in for repair
F99IPOS ramp calculationImmediate stopRamp times changed with the inverter enabled on a sinusoidal or square rampRewrite the program so ramp times change only while inhibited
F100 to F106Vibration, oil aging, brake wearDisplay fault (P) or Rapid stop (P)Diagnostic sensor warnings and faultsFind the vibration cause, schedule or perform the oil change, replace the brake lining
F107Line componentsImmediate stopNo feedback from the main contactor (regenerative power supply)Check the main contactor and control cables
F108, F109DCS fault, DCS alarmDisplay faultDCS..B safety option: configuration, voltage, switching, plausibility or communication faultsReload configuration, check supply voltage and wiring, replace the DCS..B option

F08 Speed Monitoring {#f08-speed-monitoring}

F08 is not an overvoltage on MOVIDRIVE. SEW names it “Speed monitoring” with an immediate stop response that you can reprogram. The subfault tells you which monitor tripped:

Work through the SEW measures in this order:

  1. Reduce the load and confirm the motor shaft turns freely. A jammed load keeps the drive in current limit until P501 or P503 (speed monitoring delay time) expires.
  2. Increase the delay time in P501 (motoring) or P503 (regenerative) only after you have ruled out a real overload.
  3. Check the encoder connection. If the drive runs away or trips F08 the instant you enable it, the encoder is counting the wrong direction. SEW’s instruction is to swap the A/A and B/B pairs if necessary. Confirm the encoder supply voltage at the option card.
  4. Check current limiting (P303, P313) and extend the ramps if the application cannot reach setpoint in time.
  5. Check the motor cable, motor and line phases. A missing phase shows up as F08 sub 0 long before it shows as F06.

F42 Lag Fault {#f42-lag-fault}

F42 is a positioning lag fault: the actual position fell behind the setpoint by more than the lag tolerance while IPOSplus or a positioning operating mode was active. SEW lists five causes and matching fixes:

Cause (SEW wording)Fix
Encoder connected incorrectlyCheck the encoder connection and wiring
Acceleration ramps too shortExtend the ramps
P component of the positioning controller too smallIncrease the P component
Speed controller parameters set incorrectlyReset the speed controller parameters and retune
Lag fault tolerance too smallIncrease the lag tolerance window

Also confirm that the mechanics move freely over the whole travel range. A binding axis produces F42 at the same spot every cycle; a tuning problem produces it at the highest acceleration point.

Reading and Resetting Faults

  1. Note the digits as they flash on the 7-segment display, or read the fault name on the DBG60B keypad.
  2. Connect MOVITOOLS MotionStudio (via the USB11A or RS485 interface) and open the fault memory to get the subfault and the drive state at the moment of the trip.
  3. Fix the cause. For F25, SEW says to restore factory settings, perform a reset and reset parameters. For F31 and F84 the motor must cool off before the reset.
  4. Reset with a digital input programmed as reset, the keypad, MotionStudio, or a line power cycle. The display returns to the operating display when the fault code has cleared.

When to Call SEW Service

The SEW fault list sends several codes straight to SEW Service or to repair: F01 with a defective output stage, F03 ground fault that persists after the motor and cable are cleared, F17 to F24 system faults that recur after grounding and shielding are fixed, F37, F38, F41 sub 0, F80, F94 and F98. If the drive throws any of these a second time after a power cycle, stop troubleshooting and get a replacement unit or an RMA.

Need Replacement Parts?

Match the part to the MDX60B or MDX61B size, voltage class and option cards fitted before ordering. Check SEW MOVIDRIVE braking resistors, encoder cables, DBG60B keypads and USB11A interfaces on Amazon - prices and availability change frequently.

Quick FAQ

What does SEW MOVIDRIVE fault F08 mean?

F08 is Speed monitoring. The SEW system manual lists subfault 0 (inverter in current limiting or in slip limit), 3 (system limit actual speed exceeded) and 4 (maximum rotating field speed exceeded). Causes are a speed or current controller at its limit from overload or a phase failure, an encoder that is not connected correctly or turning the wrong way, or nmax exceeded in torque control.

What does SEW MOVIDRIVE fault F42 mean?

F42 is a Lag fault in positioning. The position difference between setpoint and actual value exceeded the lag tolerance. SEW lists an encoder connected incorrectly, acceleration ramps too short, a P component that is too small, wrong speed controller parameters, or a lag fault tolerance that is too small.

How do I reset a MOVIDRIVE fault?

Fix the cause first, then reset with a digital input programmed to reset, the DBG60B keypad, MOVITOOLS MotionStudio, or a power cycle. After the reset the 7-segment display returns to the operating display. F25 needs a reset plus a parameter reset; F31 and F84 need the motor to cool first.

Is F08 on a MOVIDRIVE a DC bus overvoltage?

No. On MOVIDRIVE MDX60B/61B, DC link overvoltage is F07 and brake chopper is F04. F08 is speed monitoring. Check which drive family you have before using a MOVITRAC code list.


Need a professional? Compare Industrial repair options before replacing parts.