SEW-Eurodrive Fault F31 (TF/TH Sensor Tripped): Motor Thermistor Troubleshooting on MOVITRAC B and MOVIDRIVE B

11 min read

What this code means

SEW-Eurodrive fault F31 is TF/TH sensor tripped — the drive’s thermal motor protection input has fired. In SEW’s own words, motor winding temperature “is monitored using TF thermistors or TH bimetallic switches”: TF is a thermistor, TH is a bimetallic switch (thermostat). Wired to the drive’s sensor input, that loop is monitored by the inverter itself, and no additional monitoring unit is required. F31 means the drive no longer sees a healthy loop.

The catch, and the reason F31 wastes so much troubleshooting time, is that two completely different problems produce the identical fault. SEW’s own error list gives three causes for F31:

  1. The motor is too hot — the TF thermistor or TH thermostat has legitimately triggered.
  2. The TF/TH is not connected, or is connected incorrectly.
  3. The connection between the drive and the TF/TH on the motor is interrupted.

Cause 1 is the sensor doing its job. Causes 2 and 3 are wiring problems that look like an overheated motor to the drive, because an open loop and a hot thermistor are electrically the same thing. Your first task with any F31 is deciding which side of that line you are on.

The fault response also differs by drive family, and it matters:

That MOVIDRIVE B default has a practical consequence: an MDX drive fresh out of the box ignores the TF input. If your MOVIDRIVE B is actively tripping on F31, someone set P835 to a tripping response — almost always deliberately, to protect the motor. Do not “fix” the fault by quietly setting P835 back to “No response” unless you have confirmed the motor genuinely has no TF/TH fitted and is protected some other way.

TF thermistor vs. TH bimetallic switch

SEW fits one of two winding-temperature sensors, and knowing which one you have tells you what a healthy loop should look like at the meter:

Either way, “open” is what the drive interprets as tripped — which is exactly why a wire that fell off a terminal produces the same F31 as a cooked motor.

Where the loop lands differs by drive family, and this is worth checking before you go hunting for terminals that do not exist on your unit:

One measurement rule: check the sensor loop with a standard multimeter on a resistance range, never with an insulation tester (megger). Insulation-test voltage belongs on the motor power windings, not on the thermistor circuit — it can damage the sensor. If you megger the motor, disconnect the sensor leads first.

Common causes

Step-by-Step Fix

Safety first: the sensor terminals live in the same enclosures as lethal voltages. The drive’s DC bus holds a dangerous charge for minutes after power-off, and the motor terminal box carries the full output voltage. Lock out and tag out, wait the discharge time stated in the manual, and verify zero volts before opening either enclosure.

  1. Decide: hot motor or broken loop? Was the motor working hard when it tripped, and is the frame hot to a careful touch? If yes, treat it as real overheating (steps 2 and 7). If the motor is cool — or F31 appeared the moment a new installation was powered up — treat it as a wiring/sensor problem (steps 3-6).
  2. Let the motor cool off and reset. This is SEW’s documented first action. If the fault clears after cooling and only returns after a stretch of hard running, the sensor is telling the truth; go to step 7.
  3. Ohm out the TF/TH loop. Lock out, disconnect the sensor leads at the drive’s sensor terminals, and measure resistance across the loop with the motor cool. A cool, healthy loop reads low resistance (TF) or dead continuity (TH). An open reading (OL) with a cool motor means the fault is in the wiring or the sensor, not the temperature.
  4. Split the loop to localize the break. Open the motor terminal box and measure across the sensor terminals there. Open at the motor terminals with a cool motor points at the sensor itself or its internal leads; good at the motor but open at the drive end points at the interconnecting cable or a loose drive-side terminal. Re-land, repair, or replace as found.
  5. Check for miswiring. On a new install, confirm the sensor conductors actually go to the drive’s TF/TH input and not to a shield bar or a spare terminal, and confirm nobody ran the sensor pair inside the motor power cores where induced voltage and miswiring cause grief.
  6. No sensor fitted? Jumper it — on MOVIDRIVE B, X10:1 to X10:2. SEW’s documented provision when no TF/TH is connected on a MOVIDRIVE B is a jumper from terminal X10:1 to X10:2. Alternatively P835 can be set to “No response” where that is appropriate. Only do either when the motor truly has no TF/TH and is protected another way — see the next section before you reach for a wire link.
  7. If the motor is genuinely hot, fix the heat. Clear the fan cover and fins, verify the shaft fan is intact, reduce the load or the starts-per-hour, lengthen accel ramps, and check for a binding driven machine. For sustained low-speed duty, fit forced ventilation or size up the motor. A repeatedly overheated motor also deserves an insulation test (sensor leads disconnected first) before you trust it again.

When NOT to jumper out the sensor

The X10:1-X10:2 jumper and the P835 “No response” setting exist for motors that legitimately have no TF/TH fitted. They are not a workaround for a nuisance trip. Do not defeat the thermal sensor when:

A jumper installed “temporarily” during commissioning has a way of becoming permanent. If you must bridge the input to keep production moving after confirming a cable fault, tag the drive, log it, and schedule the cable repair.

F11 vs. F31 vs. F84: three thermal faults, three different things overheating

SEW drives report three distinct thermal problems with three different codes. Mixing them up sends you to the wrong end of the machine.

CodeWhat it watchesWhat SEW says causes itFirst fix
F11The drive itself — heat sink temperature too high, or its temperature sensor defective. On size 7 units, sub-codes 6-8 indicate the phase-module sensor for phase U/V/W; sub-code 3 is overtemperature of the switched-mode power supply.Thermal overload of the inverter; a defective phase-module temperature sensor; on MOVITRAC B, a braking resistor integrated in the heat sink adds heat.Reduce load and improve cooling; check the fan. If F11 trips when the drive is clearly not hot, the sensor is faulty (phase-module replacement on size 7). On MOVITRAC B, mount the integrated braking resistor externally.
F31The motor’s physical sensor — the TF thermistor / TH thermostat loop.Motor too hot; TF/TH not connected or connected incorrectly; the drive-to-sensor connection interrupted.Cool and reset; test and repair the sensor loop; jumper X10:1-X10:2 on MOVIDRIVE B only if no sensor is fitted.
F84The drive’s calculated thermal motor model / UL monitoring — no physical sensor required. Sub-code 2: short or open circuit in the temperature sensor (KTY type, set via P530); sub-code 3: no thermal motor model available.Motor utilization too high; IN-UL monitoring (P345/P346) triggered.Reduce load, extend ramps, allow longer pauses between cycles; check P345/P346; select a larger motor if it is undersized.

The practical read: F11 = drive hot, F31 = motor’s own sensor says hot (or its loop is open), F84 = the drive’s math says the motor is being overworked. A machine that throws F84 but never F31 is being thermally overworked in a way the model catches before the winding sensor does — that is a sizing or duty-cycle conversation, not a wiring one. A machine that throws F31 with a cool motor is a wiring problem, full stop.

When to Call a Pro

Frequently asked questions

Why do I get F31 immediately on a brand-new installation?

Because the sensor loop was never completed. On first power-up the drive sees an open TF/TH circuit and reports it as a tripped sensor. Land the TF/TH leads from the motor terminal box on the drive’s sensor input. If the motor genuinely has no TF/TH, SEW’s documented provision on MOVIDRIVE B is a jumper from X10:1 to X10:2.

The motor is stone cold but F31 won’t clear. What’s wrong?

The loop is open somewhere between the drive and the winding sensor. An open circuit is electrically identical to a hot thermistor, so the drive keeps reporting F31. Lock out, disconnect the sensor leads at the drive, and ohm the loop; then split it at the motor terminal box to find which segment is broken.

Can I just set P835 to “No response” and move on?

P835 is the documented parameter for the TF sensor response on MOVIDRIVE B, and “No response” is actually the factory default — so if the drive is tripping, someone configured that protection on purpose. Only disable it when the motor has no TF/TH fitted and has other thermal protection, and never on hoists, Ex-zone motors, or unattended machinery.

What’s the difference between F31 and F84?

F31 comes from the physical sensor in the motor windings. F84 comes from the drive’s calculated thermal motor model and IN-UL monitoring (parameters P345/P346) — it can fire with no motor sensor connected at all, and its sub-codes cover a short/open KTY sensor (sub-code 2, sensor type set in P530) and a missing thermal model (sub-code 3). F84’s cure is load, ramps, pauses, and motor sizing; F31’s cure is cooling, the sensor loop, or both.

Can I test the thermistor with an insulation tester?

No. Megger the motor windings if you need to, but disconnect the TF/TH leads first and test the sensor loop only with a standard multimeter on a resistance range. Insulation-test voltage can destroy the thermistor.

Sources

The F31 causes and responses, the X10:1-X10:2 provision, P835, and the F11/F84 comparisons were checked against these two SEW-Eurodrive PDFs.

Need this fixed instead? Describe the fault — we'll route it.

Tell us the machine and what it's doing. We read every request and reply by email. Your details go only to our dispatch inbox — see the privacy policy.

Replies come by email. Your details go only to our dispatch inbox — no account, no list.



Previous Post
SEW-Eurodrive Fault F14 (Encoder Error): Sub-Codes 0 and 25-34, Hiperface, Resolver, and X14/X15 Wiring Checks
Next Post
SEW-Eurodrive MOVIDRIVE MDX60B/61B Fault Codes: Complete Error List with Sub-Error Codes