Skip to content
Industrial Error Code Fixes
Go back

Rheem Furnace 3 Flashes - Causes & Fix

4 min read
⚡ Quick Answer

Rheem 3-flash code means the limit control circuit is open. Most common fix: replace the dirty air filter to restore airflow.

Difficulty Pro recommended
Est. time 1-3 hrs

Rheem Furnace 3 Flashes — What It Means

On Rheem gas furnaces, a 3-flash (3-blink) error code indicates the limit control circuit is open. The furnace control has detected an open safety limit and shut the unit down to prevent overheating. This is not a pressure switch issue (that is a different code). Rheem’s official documentation ties this code to conditions that cause excessive temperature rise in the heat exchanger, triggering the high-limit safety or rollout switches to open the circuit.

The furnace will not restart until the safety circuit closes and the root cause is corrected. Limit switches are designed to protect the heat exchanger from damage caused by inadequate airflow, blocked venting, or overfiring. Once tripped, the furnace remains locked out until the problem is resolved and any manual-reset switches are physically reset.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. {‘lead’: ‘Verify the 3-flash code’, ‘text’: “Watch the LED on the furnace control board and count the blinks to confirm it is exactly three flashes, then check the code chart on the unit or in your model’s literature to confirm 3 blink equals limit control circuit open.”}
  2. {‘lead’: ‘Check airflow components first’, ‘text’: ‘Inspect and replace the air filter if dirty, verify all supply registers are open, check the return-air grille for blockage, and confirm the blower is running at full speed when the furnace calls for heat.’}
  3. {‘lead’: ‘Inspect rollout switches for trip’, ‘text’: ‘Locate the manual-reset rollout switches mounted above the burners and press each reset button to see if any have tripped (you will feel a click when the button is pushed in). If one has tripped, find out why flames rolled out before resetting it.’}
  4. {‘lead’: ‘Examine the flue and heat exchanger’, ‘text’: ‘Inspect the vent pipe from the furnace to the outside for blockages (bird nests, ice, debris), then look through the burner openings or blower compartment to check heat exchanger passages for soot, rust, or obstruction.’}
  5. {‘lead’: ‘Measure manifold gas pressure’, ‘text’: ‘Connect a manometer to the manifold pressure tap on the gas valve and compare the reading during burner operation to the rating plate specification to confirm the furnace is not overfired.’}
  6. {‘lead’: ‘Test the limit control circuit’, ‘text’: ‘With power off, use a multimeter to check continuity across the limit switch terminals and through the entire limit circuit back to the control board. Replace any limit switch that does not close when cool or any rollout switch that remains open after reset.’}
  7. {‘lead’: ‘Restore power and test a full cycle’, ‘text’: ‘After correcting the root cause, turn the furnace back on and monitor a complete heating cycle to verify the burners ignite, the blower runs, and the 3-flash code does not return.’}

Parts Often Needed

PartNotes
High limit switchAmazon | Replaces a failed or stuck-open limit control. Match the exact temperature and mounting style for your Rheem model.
Manual-reset rollout switchAmazon | Typically sold individually or in sets. make sure the switch rating matches your furnace before installation.
Rheem integrated furnace control boardAmazon | Required if the control itself is faulty or if the limit circuit traces on the board are damaged. Verify your model and serial number.
Blower motor or capacitorAmazon | Needed if low airflow is traced to a weak or failing blower. Check horsepower, voltage, and rotation direction against your furnace specifications.

When to Call a Pro

Call a qualified HVAC technician if you have replaced the air filter and reset any tripped rollout switches but the 3-flash code returns immediately, if you are not comfortable working with gas appliances or electrical circuits, or if you do not have a manometer and multimeter to measure manifold pressure and test limit-circuit continuity. A technician should also investigate any rollout-switch trip, because that indicates a serious combustion or venting problem that can produce carbon monoxide if left uncorrected. If you see soot, rust, or cracks in the heat exchanger, or if the vent pipe shows signs of condensation or corrosion, stop using the furnace and call for service right away.

See Also


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.
Get Free Quotes →
Share this post on:

Previous Post
American Standard Furnace 2 Flashes - Causes & Fix
Next Post
Kenmore Microwave F6 Error Code - Causes & Fix