Kohler Generator Error Codes: Complete Guide

⚡ Quick Answer

Kohler generator error codes, fault diagnostics, and troubleshooting for Decision-Maker and APM controllers. Covers LED fault codes, LCD messages, and common Kohler generator repairs.

⚡ AT A GLANCEScroll down for full repair guide
What it meansKohler generator error codes, fault diagnostics, and troubleshooting for Decision-Maker and APM controllers. Covers LED fault codes, LCD messages, and common Kohler generator repairs.
Most likely causeMost electrical faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
Repair time10-45 minutes for basic checks
🔧Part neededAVR (residential)
Repair intent

Need this fixed instead of diagnosed?

Kohler generator error codes, fault diagnostics, and troubleshooting for Decision-Maker and APM controllers. Covers LED fault codes, LCD messages, and common Kohler generator repairs.

Kohler Generator Error Codes

Kohler industrial and residential generators (SDMO, 5E, 20RES, and R-Series) use Decision-Maker controllers on larger models and APM (Advanced Power Management) controllers on newer residential units. Faults display as error numbers on the LCD or flash patterns on the status LED.

Kohler Decision-Maker Error Codes

Error CodeFault DescriptionCommon CauseAction
1Low oil pressureOil pressure below 8 PSICheck oil level, pressure switch, wiring
2High engine temperatureCoolant temperature exceeds limitCheck coolant level, radiator, fan belt
3OverspeedEngine RPM exceeds 110% of ratedTest governor actuator, fuel supply
4UnderspeedEngine RPM below 90% of ratedCheck load, fuel pressure, air filter
5OvercrankFailed to start after programmed attemptsCheck fuel, spark, battery, starter
6OvervoltageOutput voltage exceeds 110% of ratedTest AVR, voltage adjustment pot
7UndervoltageOutput voltage below 90% of ratedTest AVR, check load, identify motor start
8Low batteryBattery voltage below 11.5V at restCharge or replace battery, test charger
9OverloadGenerator output exceeds rated capacityReduce load, check for short circuit
10Cranking faultStarter not engagingTest starter solenoid, battery cables
12Frequency faultOutput frequency outside rangeTest governor, check fuel supply
13Voltage regulator faultAVR not producing outputTest AVR fuse, field voltage, rotor
14Field overexcitationToo much voltage to rotor fieldTest AVR adjustment, regulator module
15Loss of speed signalRPM sensor signal lostCheck magnetic pickup, wiring, gap
17Battery charger faultCharger not functioningTest charger output voltage
18Fuel solenoid circuitSolenoid open or shortTest solenoid coil resistance
19Auxiliary shutdownExternal shutdown signalCheck remote shutdown wiring, contacts
20Emergency stop activeE-Stop button pressedReset E-Stop, check circuit
22High exhaust temperatureExhaust system restrictionCheck exhaust piping, muffler, insulation
23Magneto fault (gas models)No spark detectedTest ignition module, kill wire
24Camshaft sensor faultNo cam position signalTest cam sensor, wiring, timing
27Low oil pressure (pre-start)Oil pressure low before startCheck oil level, switch stuck open
34Actuator / governor faultThrottle actuator not respondingTest actuator, linkage, controller output
36Low coolant levelCoolant below sensorAdd coolant, check for leaks
44Transfer switch communication failATS not communicatingCheck ATS controller, wiring harness

Kohler APM 2-Button Controller (Residential)

Newer Kohler residential generators (5E, 20RES series) use a simple 2-button APM controller with indicator LEDs:

LED PatternMeaningAction
Red LED solidFault / shutdownRead code on LCD
Red LED flashingWarning (not shut down)Check LCD for message
Green LED solidReady / standbyNormal
Green LED flashingUnit runningNormal operation
Yellow LED solidExercise in progressNormal
Yellow LED flashingService dueSchedule maintenance

Most Common Kohler Faults

Error 5 — Overcrank

Same root causes as Generac 1200. On Kohler units, the most common sequence is: battery weak → slow crank → poor compression seal → no fire → overcrank. Start with a load test on the battery. Kohler uses Group 24 batteries on most residential units. Replace if resting voltage < 12.4V or if voltage drops below 10V under crank.

Error 3 — Overspeed

Kohler Overspeed typically triggers at 110% of rated RPM (1980 RPM on 1800 RPM generators, or 3960 on 3600 RPM models). Common cause on gas generators: the demand regulator diaphragm cracks, allowing too much fuel at deceleration. On newer units, check the electronic governor actuator for binding linkage. A failing actuator will show erratic hunting before the overspeed event.

Error 13 — Voltage Regulator Fault

The Kohler voltage regulator (AVR) supplies DC excitation to the rotor. If the regulator fails, the generator runs but produces no voltage. Quick test: engine running, measure DC voltage across the rotor brushes — should be 5–40 VDC depending on load. Zero volts = AVR not exciting the rotor. Common Kohler AVR part numbers: GM71908 (5–50 kW) and GM72405 (60–200 kW).

Parts Reference

PartApprox CostNotes
AVR (residential) Kohler$120–$250GM71908 for 5E/20RES
AVR (industrial) Kohler$250–$600GM72405-series
Battery charger board$80–$150GM69463
Magnetic pickup sensor$30–$50Kohler A-467300
Governor actuator$150–$400Kohler A-435316
Fuel solenoid (NG/LP)$50–$100Kohler A-256914-S

Need Replacement Parts?

Finding the right replacement parts for your equipment is critical to getting it running again. Check current prices on Amazon — prices and availability change frequently.

Transfer Switch Notes

Kohler uses KMC (Kohler Modular Controller) transfer switches. Common ATS faults: RXT controllers that lose programming after a firmware glitch, and GFI-neutral bonding issues that cause nuisance trips on newer RXT models. If the generator runs but the house doesn’t transfer, the ATS controller likely needs reprogramming.