Skip to content
Industrial Error Code Fixes
Go back

Heatcraft Walk-In Cooler Error Code Guide — Causes & Fixes

⚡ Quick Answer

Heatcraft walk-in cooler and freezer error codes: what each alarm means and how to fix it.

Heatcraft Walk-In Cooler Error Codes — What They Mean

Heatcraft Refrigeration Products (brands: Bohn, Larkin, Climate Control, Inter-City) makes evaporator coils and unit coolers for walk-in coolers and freezers across food retail and foodservice. Heatcraft unit coolers with electronic controls (EC controllers) display alarm codes when faults are detected.

AlarmMeaningUrgency
1High temperature alarmHigh
2High discharge temperatureHigh
3Low suction pressureMedium
4High suction pressureMedium
5Defrost termination faultMedium
6Evaporator fan motor faultHigh
7Temperature sensor faultMedium

Jump to Fix

Most Common Heatcraft Walk-In Alarms and Fixes {#fix}

Alarm 1 — High Temperature

Box temperature exceeded setpoint. Immediate action required if product is at risk. Check: evaporator fan motors running, coil not iced over, condensing unit operating, door seals intact.

Alarm 2 — High Discharge Temperature

Discharge line temperature too high. Most common causes: dirty condenser on condensing unit, condenser fan failure, refrigerant overcharge, restricted liquid line.

Alarm 3 — Low Suction Pressure

Low refrigerant charge is most common. Also check: dirty evaporator coil (restricted airflow), TXV malfunction (sticking closed), or liquid line filter-drier restriction.

Alarm 5 — Defrost Termination Fault

Defrost failed to terminate properly. Check defrost termination thermostat and heater continuity. On air defrost systems, check fan operation and ambient conditions.

Alarm 6 — Fan Motor Fault

Evaporator fan motor failure or overload. Check motor for seized bearings and correct rotation direction.

Alarm 7 — Temperature Sensor Fault

Air temperature sensor open or shorted. Test sensor resistance and replace if out of spec.

Parts Often Needed

PartNotes
Evaporator fan motorAmazon | Match to Heatcraft unit cooler model
Air temperature sensorAmazon | Replace if resistance out of spec
Defrost heaterAmazon | Replace if open circuit
Defrost termination thermostatAmazon | Replace if open at room temp

When to Call a Pro

Alarms 3 and 4 (pressure faults) indicate refrigerant circuit issues requiring an EPA 608-certified technician. All refrigerant work requires proper recovery and certification.


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.