Skip to content
Industrial Error Code Fixes
Go back

Goodman 3 Flash Error Code — Pressure Switch Stuck Open Fix

⚡ Quick Answer

Goodman 3 flash error code means the pressure switch is stuck open. This guide covers every cause and fix for the 3-blink fault on Goodman, Amana, and Daikin furnaces.

⚡ AT A GLANCEScroll down for full repair guide
What it meansGoodman 3 flash error code means the pressure switch is stuck open. This guide covers every cause and fix for the 3-blink fault on Goodman, Amana, and Daikin furnaces.
Most likely causeMost hvac faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
Repair time10-45 minutes for basic checks
Repair intent

Need this fixed instead of diagnosed?

Goodman 3 flash error code means the pressure switch is stuck open. This guide covers every cause and fix for the 3-blink fault on Goodman, Amana, and Daikin furnaces.

Error Code: Goodman 3 Flashes

What it means: Three flashes on a Goodman furnace diagnostic LED indicates the pressure switch is stuck in the open position. Goodman uses a 2-second pause followed by rapid blinks to communicate fault codes — three blinks, pause, three blinks. The same code applies to Amana and Daikin-branded furnaces built on the Goodman platform.

The pressure switch is a safety device that verifies the inducer motor is generating adequate negative pressure (draft) before allowing the gas valve to open. When the switch is stuck open — meaning it never closes and signals “safe to ignite” — the board refuses to start the burners. This protects against carbon monoxide buildup from a blocked flue or failed inducer.

Common Causes

Step-by-Step Fix {#step-by-step-fix}

  1. Check the condensate drain first. On 90%+ furnaces, locate the condensate trap (typically a clear plastic J-trap or U-trap on the side of the furnace cabinet). Look for standing water or blockage. Pour water into the drain and confirm it flows freely. If blocked, use a wet/dry vacuum on the drain line outlet to clear the clog. This resolves roughly 40% of 3-flash codes on high-efficiency Goodman furnaces.

  2. Inspect all condensate hoses and pressure switch hoses. With the furnace off, trace the small-diameter rubber tubes from the inducer housing to the pressure switch. Look for cracks, kinks, or loose connections at either end. Squeeze the hose along its length — a collapsed or cracked hose won’t spring back properly. Replace any suspect hose with matching diameter rubber tubing from a hardware store.

  3. Verify the inducer motor is running. With power restored and a call for heat active, listen for the inducer to start first — it should spin up before anything else happens. A healthy inducer sounds smooth and consistent. If you hear grinding, vibration, or the motor struggles to reach speed, suspect a failing inducer capacitor (cheap fix, ~$10) or a worn inducer motor.

  4. Test the inducer capacitor. Shut off power. Locate the small oval capacitor on or near the inducer motor. Use a capacitor tester or a multimeter with capacitance function to test it against the rated value printed on the capacitor (typically 3–7 µF for Goodman inducers). A reading more than 10% below rated value means the capacitor needs replacement.

  5. Test the pressure switch with a manometer or hand pump. Disconnect the hose from the pressure switch inlet. Using a hand vacuum pump or your mouth (gently), apply negative pressure to the switch port. You should hear a distinct click and see continuity on a multimeter across the switch terminals when sufficient vacuum is applied. No click = failed switch.

  6. Check the flue and intake pipes outside. Go outside and visually inspect the white PVC pipes exiting the building. Look for bird nests, wasp nests, ice, leaves, or any blockage. Both the flue pipe and the combustion air intake must be completely clear. On windy days, check that the pipe terminations aren’t too close together or too close to a wall — recirculated exhaust can back-pressure the system.

  7. Replace the pressure switch if all else checks out. The Goodman pressure switch B1370112 fits most GMSS, GMEC, and AMVC series furnaces (~$35 at Repair Clinic). Confirm the switch rating (typically -0.65 in. W.C. or -0.45 in. W.C.) matches the original before ordering.

  8. Run the furnace through three complete heat cycles after any repair to confirm the 3-flash code is resolved.

Parts That May Need Replacement {#parts-that-may-need-replacement}

PartPart NumberTypical CostWhere to Buy
Pressure switchB1370112$30–$45RepairClinic
Inducer motor capacitorB175-1068$8–$15RepairClinic
Inducer motor assemblyB1859005$120–$180RepairClinic
Condensate drain trapB1787419$12–$20RepairClinic

Technician Tips

Goodman furnaces use a simple LED flash system on the control board. The diagnostic LED is usually visible through the blower compartment window. Count the flashes between pauses — that’s your error code. One flash = normal operation. Two flashes = pressure switch fault. Three flashes = limit switch. Four flashes = flame sensor. Goodman flame sensors are notorious for carbon buildup — cleaning with emery cloth every 2-3 years prevents most lockout calls. The control board on GMS8 and GMSS9 models is particularly sensitive to voltage fluctuations — if you see multiple different codes, check the transformer output (should be 24VAC ±10%).

Prevention: Install a whole-house surge protector on the furnace circuit to prevent board damage from power spikes.

Need Replacement Parts?

Finding the right replacement parts for your equipment is critical to getting it running again. Check current prices on Amazon — prices and availability change frequently.

When to Call a Professional

If the pressure switch, inducer motor, and condensate drain all check out and the 3-flash code persists, the problem may be inside the heat exchanger — a cracked secondary heat exchanger can upset combustion airflow in ways that prevent the pressure switch from closing. Cracked heat exchanger diagnosis requires combustion analysis equipment and should be performed by a licensed HVAC technician. A cracked heat exchanger also poses a carbon monoxide risk and should be treated as a safety issue, not just a repair issue.

Pro tip: Before buying a new pressure switch, take off the hose and blow through the switch port — you should feel resistance and hear a click when vacuum is applied. If you can blow freely with no click, the diaphragm is already blown and the switch is trash. This 10-second test saves the round trip of installing a new switch only to find the real problem was the inducer.

See Also


Need a professional? Compare certified HVAC repair options before replacing parts.
Get Repair Quotes
Share this post on:

Previous Post
Fanuc Alarm 401 — Servo Axis Overload Fix
Next Post
Fanuc Alarm 300 — APC Alarm Fix (Absolute Encoder)