EVAPCO Cooling Tower Fault Codes Guide — AT / LSTE Series

⚡ Quick Answer

EVAPCO cooling tower fault codes and alarm conditions for AT, LSTE, and closed-circuit evaporative coolers: causes, diagnostics, and troubleshooting steps.

EVAPCO Cooling Tower Fault Codes — Quick Reference

EVAPCO cooling towers and evaporative condensers with PMC (Packaged Mechanical Component) control panels or VFD systems generate fault conditions from motor protection, temperature monitoring, and water management systems.

FaultMeaningQuick Fix
Fan Motor FaultMotor overload or tripCheck motor amps, bearings, and connections
High Leaving Water TempLeaving water above setpointCheck fan operation and load balance
Low Basin LevelMakeup water not keeping upCheck makeup valve and inlet pressure
High Basin LevelOverflow conditionCheck float valve and drain
Vibration AlarmExcessive vibration detectedInspect fan, shaft, and bearings
Freeze AlarmBasin approaching freeze tempCheck heater and circulation
VFD FaultDrive fault on fan motorRefer to VFD fault code
Motor Phase FaultPhase loss or imbalanceCheck supply fuses and connections

Most Common Faults

Fan Motor Fault

EVAPCO towers use axial or centrifugal fans. Motor overloads are caused by: ice buildup on fan blades in winter, worn motor bearings increasing load, blade pitch set incorrectly, and belt slippage on belt-drive models. Check motor amperage and compare to nameplate. Inspect bearings for roughness or excessive play.

High Leaving Water Temperature

If the tower is not maintaining approach temperature, check: fan speed (VFD may be in low-speed or manual mode), drift eliminators and distribution basins for scale buildup, and whether the heat load has increased beyond the tower’s rated capacity.

Freeze Alarm

Cold weather tower operation is critical. EVAPCO towers use basin heaters to prevent freeze-up. Check the heater element with an ohmmeter. Verify the freeze protection thermostat setpoint. EVAPCO recommends maintaining basin water temperature above 35°F.

EVAPCO Closed-Circuit Coolers (LSTE)

EVAPCO LSTE closed-circuit evaporative coolers add additional monitoring:

Maintenance Schedule

IntervalTask
WeeklyCheck basin level and water quality
MonthlyInspect fan operation and motor amps
AnnuallyClean tube bundle (LSTE), inspect fill, check basin sealant

Jump to Fix

When to Call a Pro

EVAPCO service centers provide commissioning, inspection, and component replacement. Contact EVAPCO at 1-410-756-2600.