Eaton Circuit Breaker Fault Codes - Complete Guide

⚡ Quick Answer

Eaton Magnum DS, PowerDefense, and Cutler-Hammer circuit breaker fault codes and trip indicators: causes and reset procedures.

Eaton Circuit Breaker Fault Codes - Quick Reference

Eaton Magnum DS and PowerDefense (formerly Cutler-Hammer) air circuit breakers use the EATON/Digitrip RMS 810/910 and PowerNet trip units. Faults are shown on LED panels, trip cause indicators, and via PowerNet communication.

Fault / IndicatorMeaningQuick Fix
Trip - Long Time (LT)Sustained overloadReduce load, check current
Trip - Short Time (ST)Short-circuit delay zoneLocate and clear fault
Trip - Instantaneous (INST)High-level fault currentInspect load and wiring immediately
Trip - Ground Fault (GF)Earth fault (Digitrip 5/8/9)Find ground fault source
Trip - Neutral OvercurrentNeutral conductor overloadedCheck for harmonics
TEST - TripManual trip test resultNormal - reset and close
Zone Selective InterlockDownstream breaker trippedFind tripped downstream breaker
PowerNet: Comm FaultNetwork communication lostCheck wiring to PowerNet
Maintenance IndicatorInspection interval reachedSchedule maintenance
ALARM - OverloadPre-trip warningReduce load before trip

Most Common Faults

Long Time Overload Trip

Check actual load current on all three phases. On three-phase systems with high harmonic content (VFD loads, UPS systems), neutral currents can be very high - this can cause long-time trips even when phase currents look normal. Verify Digitrip settings match the conductor and equipment ratings.

Zone Selective Interlock (ZSI)

Eaton Magnum breakers support ZSI - when a downstream breaker detects a fault, it signals upstream breakers to add a short-time delay, allowing the closest breaker to clear the fault selectively. If ZSI faults are appearing, check the ZSI wiring between breakers and verify ZSI is enabled in all breaker settings.

Ground Fault Trip

Eaton Digitrip 810/910 ground fault protection trips when ground fault current (measured via a core balance CT or summation of phase currents) exceeds the Ig setting. Check for leakage current paths in the load - especially motors with degraded winding insulation and cables exposed to moisture.

Instantaneous Trip

An instantaneous (INST) trip on Eaton breakers occurs at 2–10× rated current. This is nearly always a fault in the load circuit. Inspect the load terminals, cables, and equipment before attempting a reset.

Parts Often Needed

PartNotes
Digitrip RMS moduleAmazon | Replace on electronics failure
Arc chutesAmazon | Inspect after fault trips
Auxiliary/alarm contactsAmazon | Replace when worn
PowerNet communication moduleAmazon | Replace on comm fault
Spring charging motorAmazon | Replace on slow charge or no-charge

When to Call a Pro

Magnum DS maintenance, contact inspection, and trip unit calibration require training. Never reset after an instantaneous trip without an electrician inspecting the load circuit.