Danfoss FC302 Alarm 43 - Causes & Fix

3 min read

Independent. We don't sell parts, so we tell you when not to buy one.

⚡ Quick Answer

Alarm 43 means an external fault or interlock signal is active. Check E-stop, safety contacts, and control wiring first.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Danfoss FC302 Alarm 43 — What It Means

Alarm 43 on the Danfoss FC302 VFD indicates an external fault or external interlock signal is active. This is not an internal drive failure. The drive is reporting that something outside the VFD is opening the run-enable or interlock chain, such as a safety contact, E-stop, or field device contact. The drive stops and displays the alarm because it is being told to trip by an external signal.

In practical terms, the FC302 is responding to a deliberate external shutdown command or an unintended open circuit in your safety or permissive wiring. The fault does not point to a problem inside the drive itself but rather to the control wiring, field devices, or safety chain that feeds the drive’s external fault input.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Identify the external fault circuit on your machine schematic and determine which contact, relay, or terminal is assigned to the interlock or alarm chain for the FC302.
  2. Check the external fault input status at the drive control terminals and verify whether the interlock signal is open or closed using a multimeter or the drive’s digital input status display.
  3. Inspect all field wiring in the interlock chain for loose terminal screws, broken conductors, corrosion at connections, or mislanded wires at the drive control terminals.
  4. Verify the safety circuit and permissives by checking that E-stops are reset, HOA switches are in the correct position, and all bypass or run-enable contacts are closed.
  5. Isolate the field circuit section by section to find which device is opening the chain by temporarily bypassing one contact or switch at a time until the open device is identified.
  6. Reset the alarm only after the external circuit is restored and all interlock contacts are confirmed closed and functioning.
  7. If the alarm persists with the external circuit proven closed, check the drive’s control input wiring and control card I/O condition, and consider that the control card itself may have a fault if the input circuit is verified correct.

Parts Often Needed

PartNotes
External interlock contact or safety relayAmazon | Replace if the field circuit device (E-stop, pressure switch, flow switch, or safety relay) is found to be defective or stuck open.
Field wiring terminal blocks and connectorsAmazon | Replace any damaged terminal blocks, corroded connectors, or broken wire sections in the interlock chain.
Danfoss FC302 control card / control PCBAmazon | Replace only if the external circuit is verified closed and the drive still misreads the input condition, indicating a control card fault.

When to Call a Pro

Call a qualified electrician or automation technician if you cannot locate the open contact in the interlock chain, if the machine schematic is unavailable or unclear, or if the alarm persists after verifying all external wiring and contacts are correct. A technician with a schematic and multimeter can systematically trace the interlock circuit and identify which field device or wiring segment is opening the chain. Also call a professional if you suspect a control card fault, as drive control board diagnosis and replacement require familiarity with VFD parameter backup, proper handling of static-sensitive components, and verification of correct I/O configuration after card replacement.