Danfoss FC302 Alarm 40 - Causes & Fix

3 min read

Independent. We don't sell parts, so we tell you when not to buy one.

⚡ Quick Answer

Alarm 40 on a Danfoss FC302 is a digital output overload on terminal 27. Check for shorts or excessive load on that terminal.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Danfoss FC302 Alarm 40 — What It Means

Alarm 40 on a Danfoss FC302 VFD means overload of digital output terminal 27. The drive has detected that terminal 27 is sourcing or sinking more current than allowed, or the connected circuit is effectively shorted. This fault is tied to parameters 5-00 (Digital I/O Mode) and 5-01 (Terminal 27 Mode). The drive is protecting itself from damage to the output stage.

This is not a motor earth fault or a power-stage problem. It is strictly a digital I/O issue on terminal 27. The fault points to either external wiring or device problems connected to that terminal, or incorrect configuration of how the terminal is being used. In most cases, the issue is in the field wiring or the connected load, not inside the drive itself.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Disconnect power to the drive and wait for stored energy to discharge before working on any terminals.
  2. Remove the wiring and load from terminal 27 completely. Restore power and check if Alarm 40 clears.
  3. Inspect the removed wiring and external device for shorts, pinched conductors, incorrect terminations, or signs of internal failure in the connected load.
  4. Check parameter 5-00 (Digital I/O Mode) and parameter 5-01 (Terminal 27 Mode) in the drive menu. Verify both settings match the intended function and external circuit requirements for terminal 27.
  5. Reconnect the wiring to terminal 27 after repairs or verification. Power up the drive and test for normal operation without the alarm.
  6. Cycle power to the drive if Alarm 40 persists with terminal 27 unloaded. If the alarm returns with no external load, the control card or I/O section may be defective.
  7. Replace the control card or contact Danfoss if the fault remains after all external causes are ruled out and terminal 27 is disconnected.

Parts Often Needed

PartNotes
Field wiring for terminal 27Amazon | Replace if conductors are shorted, pinched, or damaged.
External relay or device connected to terminal 27Amazon | Replace if the connected load is internally shorted or draws excessive current.
Danfoss FC302 control cardAmazon | Required if Alarm 40 persists with terminal 27 unloaded and after power cycle. Consult Danfoss for part number specific to your drive model.

When to Call a Pro

Call a qualified technician or controls specialist if you are not comfortable working with VFD wiring or digital I/O circuits. If Alarm 40 continues after you have removed and checked all external wiring and loads on terminal 27, and the fault returns after a power cycle with nothing connected, the control card is likely defective and requires factory replacement or repair. VFD repairs involving internal boards should be done by trained personnel to avoid voiding warranties or creating safety hazards.