Danfoss FC302 AL-158 Fault - Causes & Fix

4 min read

Independent. We don't sell parts, so we tell you when not to buy one.

⚡ Quick Answer

AL-158 is not a documented Danfoss FC302 code. Likely Alarm 13/14/16 (DC bus undervoltage). Check input power and motor windings first.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Danfoss FC302 AL-158 Fault — What It Means

There is no specific AL-158 fault code documented for the Danfoss FC302 VLT AutomationDrive. Danfoss FC302 alarms are numbered sequentially (for example Alarm 13, 14, 16, 38, 60) and do not include 158. The code may be a misread or typo. The most likely match is Alarm 13, 14, or 16, which indicates DC bus undervoltage. This means the DC bus voltage has dropped below the minimum threshold (typically around 200V) required for proper motor control. The drive shuts down to protect itself and the motor from damage caused by insufficient voltage.

Before You Replace Anything

Technicians often replace the power board or IGBT modules before testing the motor windings. A simple megohm test (reading below 2 MΩ to ground indicates motor insulation failure) and running the drive unloaded can isolate whether the fault is internal to the drive or in the motor and cabling.

Jump to Fix

Common Causes

Quick Diagnosis

Answer these to narrow it down fast.

Does the alarm persist when you run the drive with the motor disconnected?
Yes: The fault is internal to the drive (power board, IGBTs, or DC link capacitors). Call a VFD technician for power board diagnostics.
No: The problem is in the motor, motor cables, or load. Proceed to test motor winding insulation and cable continuity.
Does a megohm test show motor winding resistance to ground below 2 MΩ?
Yes: Motor insulation has failed. Replace or rewind the motor.
No: Motor windings are intact. Check cable connections, input voltage during startup, and parameter 1-24 for correct motor current rating.
Does input line voltage drop below the rated minimum during motor startup?
Yes: Incoming power supply is inadequate or shared with high-draw equipment. Upgrade supply or isolate the VFD on a dedicated circuit.
No: Check for mechanical overload, loose output connections, or incorrect torque limit settings in parameter 14-25.

Step-by-Step Fix

  1. Power down the VFD and lock out the main disconnect. Wait at least 5 minutes for DC bus capacitors to discharge before opening the enclosure.
  2. Disconnect the motor from the VFD output terminals (U, V, W). Run the drive unloaded and observe if the alarm clears. If the fault persists, the issue is internal to the drive.
  3. Perform a megohm test on the motor windings to ground using an insulation tester. Readings below 2 MΩ indicate insulation failure and require motor replacement or rewinding.
  4. Measure incoming line voltage at the VFD input terminals during operation and motor startup. Look for voltage sags or drops below the rated minimum (consult your model’s input voltage range).
  5. Inspect all terminal connections at the input, output, and control terminals. Tighten any loose connections and clean corroded terminals with electrical contact cleaner.
  6. Verify parameter 1-24 (motor nominal current) matches the motor nameplate rating exactly. Incorrect settings cause the VFD to draw excessive current.
  7. Check parameter 15-32 for extended alarm codes that provide additional diagnostic information. Cross-reference with the FC302 manual for specific fault details.
  8. Test output to motor for short circuits. With the motor disconnected, measure resistance from each output terminal (U, V, W) to ground. Any low resistance indicates a shorted power board or output stage.

Parts Often Needed

PartNotes
Danfoss FC302 power board assemblyAmazon | Rectifier and inverter section with IGBT modules and DC link capacitors. Required if internal fault persists with motor disconnected.
IGBT module setAmazon | Individual replacement IGBTs for the inverter section. Consult your drive model and power rating for correct part number.

When to Call a Pro

Call a VFD technician if the alarm persists with the motor disconnected (indicating internal drive failure), if you are not comfortable working with high-voltage DC and AC circuits, or if you lack the tools to perform megohm testing and DC bus diagnostics. Power board and IGBT replacement requires precise component matching, proper thermal compound application, and testing under load. Technicians can also perform parameter optimization and input power quality analysis to prevent future faults. If the motor has failed insulation, a motor shop can perform rewinding or you may need a replacement motor matched to the drive’s power and voltage rating.

Rough cost: A pro service call runs about $300-800.