Danfoss FC302 AL-136 Fault - Causes & Fix

4 min read

Independent. We don't sell parts, so we tell you when not to buy one.

⚡ Quick Answer

AL-136 is not a valid FC302 code. The likely code is Alarm 13 (overcurrent). Most common fix: verify motor parameter 1-24 matches motor rating.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Danfoss FC302 AL-136 Fault — What It Means

No fault code AL-136 exists in Danfoss FC302 documentation. The drive uses numeric alarm identifiers like Alarm 13, Alarm 14, and Alarm 4. The most probable match is Alarm 13, which indicates output current exceeding safe operating thresholds during normal operation or acceleration. This fault triggers when current builds beyond the drive’s rated capacity (typically 150–160% of nominal current sustained for several seconds), protecting the drive from thermal overload and IGBT damage. The fault is not an instantaneous short circuit but rather a gradual current buildup that exceeds safe limits.

Alarm 13 protects the drive hardware by shutting down before heat damages the inverter module. The drive monitors current through internal sensors and compares it against parameter settings. When the threshold is crossed for too long, the alarm latches and stops the motor. The fault can originate from mechanical issues on the motor side, incorrect parameter configuration, or internal drive component failure.

Before You Replace Anything

Technicians often replace the entire inverter power module when Alarm 13 appears, but most cases stem from wrong parameter 1-24 settings or mechanical motor overload. Always disconnect the motor and run the drive unloaded first to isolate whether the fault is in the drive or the motor circuit.

Jump to Fix

Common Causes

Quick Diagnosis

Answer these to narrow it down fast.

Does the drive display Alarm 13 (not AL-136) on the keypad?
Yes: Proceed with Alarm 13 diagnostics below.
No: Check your drive model documentation for the exact code displayed, as AL-136 does not exist in FC302 manuals.
Does Alarm 13 clear when you disconnect the motor cables and run the drive unloaded?
Yes: The fault is in the motor, motor cables, or mechanical load. Inspect motor connections, test winding insulation, and check for mechanical binding.
No: The fault is internal to the drive. Check for failed IGBTs, current sensors, or internal wiring damage.
Does parameter 1-24 (motor nominal current) exactly match the motor nameplate current rating?
Yes: Parameter is correct. Move to mechanical and motor insulation testing.
No: Set parameter 1-24 to the exact nameplate current and reset the alarm. This fixes most Alarm 13 cases.

Step-by-Step Fix

  1. Power down the drive and lock out the disconnect. Wait at least five minutes for capacitors to discharge before opening the enclosure.
  2. Check parameter 1-24 on the keypad. Compare the value to the motor nameplate nominal current. If they do not match exactly, enter the correct current value and save.
  3. Verify all motor data parameters (120–125 in some firmware versions) match the motor nameplate for voltage, frequency, speed, and power factor.
  4. Disconnect the motor cables at the drive output terminals. Power up the drive and attempt to run it unloaded at low speed. If Alarm 13 persists, the drive has an internal fault (proceed to step 7).
  5. Inspect motor wiring and connections if the drive runs unloaded without fault. Tighten all terminals, clean any corrosion, and verify continuity from drive outputs to motor windings.
  6. Perform a megohm insulation test on the motor windings to ground. Readings below 2 megohms indicate insulation failure requiring motor repair or replacement.
  7. Check cooling and internal components if the drive faults while unloaded. Verify all fans operate, clean blocked vents, and inspect for damaged current sensors or IGBT modules. Log extended alarm data in parameter 15-32 for diagnostic codes.
  8. Reset the alarm by pressing the Reset button or cycling power. Reconnect the motor and run a test cycle under normal load. Monitor current on the display during acceleration.

Parts Often Needed

PartNotes
Danfoss FC302 power card / IGBT moduleAmazon | Order by drive frame size and voltage rating stamped on the module cover.
Danfoss FC302 control boardAmazon | Required if current sensor circuits have failed, less common than power module failures.
Drive cooling fan assemblyAmazon | Match the part number on the fan housing, varies by drive frame size.

When to Call a Pro

Call a qualified VFD technician or industrial electrician if the alarm persists after you have verified parameter 1-24 and checked motor connections. Internal drive faults require high-voltage diagnostic tools, IGBT module testing, and current sensor calibration that are not safe for untrained personnel. Also call a pro if motor insulation testing shows readings below 2 megohms, as motor rewind or replacement requires specialized equipment. If the motor is mechanically jammed or you suspect bearing failure, a motor shop or mechanical technician should inspect the shaft and bearings before you restart the drive. Do not attempt to replace IGBT modules or control boards without proper training in handling high-voltage DC bus capacitors and electrostatic-sensitive components.

Rough cost: A pro service call runs about $150-400 for parameter adjustment and diagnostics, $800-2,500 if IGBT module replacement is needed.


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.