Automated Logic WebCTRL Fault Codes - Complete Guide

⚡ Quick Answer

Automated Logic WebCTRL BAS fault codes and alarms for ALC controllers: communication failures, sensor faults, and troubleshooting steps.

Automated Logic WebCTRL Fault Codes - Quick Reference

Automated Logic (Carrier subsidiary) WebCTRL uses BACnet controllers (MCB, LGR, VMA, ZN series) and SiteBuilder software. Alarms display in the WebCTRL Alarm Manager and via e-mail/SMS notification.

AlarmDeviceMeaningQuick Fix
Controller OfflineMCB/LGRController not respondingCheck power and network
Sensor Out of RangeVMA/ZNSensor reading exceeds limitsCheck sensor and wiring
Communication FaultAllBACnet communication lostCheck MS/TP or BACnet IP
Fan Status AlarmAHUFan command/status mismatchCheck fan and status input
Discharge Air FaultAHUDischarge air out of rangeCheck coil valves and economizer
Freeze AlarmAHULow temperature detectedCheck heating coil and OA damper
Override ActiveAnyManual override in effectClear override via WebCTRL
Valve FaultAHUActuator position faultCheck actuator wiring
Occupancy FaultZoneOccupancy schedule errorCheck schedule configuration
WebCTRL Server FaultServerServer application errorRestart WebCTRL service

Most Common Faults

Controller Offline

An ALC controller going offline in WebCTRL typically indicates a network issue or a power problem. Check that the controller is powered (status LED on), then ping the controller’s IP address from the WebCTRL server. BACnet MS/TP trunk faults cause cascading offline alarms for all devices on that trunk.

Sensor Out of Range

ALC controllers accept UI (universal input) configured as thermistor, 0–10V, 4–20mA, or dry contact. A sensor out of range alarm means the raw input is outside the calibrated range. In SiteBuilder, check the input type configuration matches the physical sensor. A broken thermistor wire reads the same as a short and will be outside range.

Freeze Alarm

WebCTRL freeze alarms from AHU applications latch and require acknowledgment plus reset at the controller. The freeze strategy (close OA damper, open HW valve, stop fan or not) is configured per-program. After resolving the freeze condition, reset the alarm in WebCTRL and verify the OA damper returned to controlled position.

WebCTRL Server Fault

WebCTRL runs as a Windows service. If the service crashes or fails to start after an update, check the WebCTRL log files in the install directory. Common causes: Java heap size too small, SQL database connection failure, or a corrupt WebCTRL database. ALC recommends quarterly database backups.

Parts Often Needed

PartNotes
MCB/LGR controllerAmazon | Replace on hardware fault
VMA VAV controllerAmazon | Replace on hardware fault
Zone sensor (ZS)Amazon | Replace on sensor fault
Damper actuatorAmazon | Replace on valve/damper fault
WebCTRL server hardwareAmazon | Replace on server fault

When to Call a Pro

WebCTRL server administration, database management, and BACnet network configuration require Automated Logic-certified technicians. An incorrect network change can disable multiple buildings simultaneously.