ABB ACS880 Fault 2310 - Overcurrent Diagnosis and Fix

⚡ Quick Answer

Diagnose and fix the ABB ACS880 fault 2310 overcurrent fault. Covers motor overload, short circuit, acceleration ramp, and inverter module causes with step-by-step fixes.

The ABB ACS880 fault 2310 is an overcurrent fault — the drive has detected that the output current exceeded the instantaneous trip threshold. Unlike a sustained overload fault (like 2350), fault 2310 is a fast-acting protection that trips in microseconds when current spikes above a safe level. It protects both the motor and the drive’s IGBT power modules from damage caused by a sudden high-current event.

This guide covers all causes of fault 2310 on the ACS880, how to distinguish between motor-side and drive-side causes, and the step-by-step procedure for restoring normal operation.

What Does ACS880 Fault 2310 Mean?

Fault 2310 means the ACS880 measured a peak phase current exceeding the overcurrent trip limit. The ACS880 monitors output current on all three phases continuously. When any phase current exceeds approximately 3.5–4x the drive’s rated current (depending on configuration), fault 2310 trips immediately.

The ACS880 stores a fault snapshot in its fault history (accessible via the ACS880 control panel or DriveStudio software), including:

This data is critical for diagnosis — look at it before changing any parameters.

Related faults to distinguish from 2310:

FaultMeaning
2310Overcurrent (instantaneous trip)
2330Earth (ground) fault
2340Short circuit
2350Overcurrent (thermal overload)
3210DC overvoltage
3220DC undervoltage

Common Causes

The most common causes of ACS880 fault 2310 are:

  1. Acceleration ramp too aggressive — the motor can’t accelerate fast enough; current spikes during ramp
  2. Short circuit on output cables or motor windings — phase-to-phase or phase-to-ground short
  3. Motor bearings seized or mechanical jam — load suddenly demands more torque than the drive can provide without spiking current
  4. Incorrect motor parameters — motor nominal values programmed incorrectly lead to poor current regulation
  5. Drive IGBT module failure — internal fault in the power electronics
  6. Cable length too long without output reactor — long output cables create distributed capacitance that causes capacitive charging current spikes during switching

How to Fix It

Step 1: Check the Fault Snapshot

Before touching anything, read the fault snapshot from the ACS880:

Key values to record:

Step 2: Check Motor and Output Cable Insulation

With the drive powered OFF and locked out:

Step 3: Check Motor Shaft for Mechanical Jam

With power OFF, attempt to rotate the motor shaft by hand. It should rotate smoothly with resistance appropriate for the load. If it’s locked or very stiff:

A seized load or failed motor bearing causes an instantaneous torque demand spike on startup that exceeds 2310’s trip threshold.

Step 4: Adjust Acceleration Ramp Time

If the motor and cables are healthy, the most common cause of ACS880 fault 2310 is an acceleration ramp time that’s too short for the driven load.

For high-inertia loads (large fans, centrifuges, large pumps), acceleration times of 30–120 seconds are common. Don’t use a 5-second ramp on a 50,000 kg-cm² inertia load.

Step 5: Verify Motor Nameplate Parameters

The ACS880 uses motor nominal parameters to calculate current limits and control gains. If these are entered incorrectly, the drive’s current regulator is tuned for the wrong motor and may generate current spikes.

Check parameter group 99 (Motor Data) against the motor nameplate:

Correct any discrepancies. After changing motor data, re-run the motor ID run (parameter 99.13).

Step 6: Check for Long Cable Effects

Output cable runs longer than 100 meters (roughly 330 feet) can cause capacitive charging current spikes during IGBT switching transitions. These spikes appear as overcurrent events to the drive’s protection circuitry.

Step 7: Check IGBT Gate Driver / Power Module

If fault 2310 occurs immediately at power-on before any output, or occurs randomly with no load, the drive’s internal IGBT power module may have failed.

Parts You May Need

PartUseAmazon Link
Megohmmeter / Insulation Resistance TesterTest motor winding and cable insulationView on Amazon
True RMS Clamp MeterMeasure output current during drive operationView on Amazon
ABB du/dt Output ReactorProtect against long cable capacitive current spikesView on Amazon
Motor Shaft Coupling (flexible)Replace coupling if mechanical transmission is causing jamView on Amazon

When to Call a Pro

FAQ

Q: The ACS880 faults on 2310 only when starting under load at low frequency. What’s wrong?

A: This is a classic sign of an acceleration ramp that’s too fast combined with a high starting torque demand. In the fault snapshot, if current is near trip level and frequency is 1–10 Hz, increase the acceleration time or enable the ACS880’s speed controller anti-windup function. Also verify that the current limit parameters (30.17 Maximum current) are set appropriately for your motor.

Q: ACS880 fault 2310 trips randomly during normal operation, not at startup. What causes random overcurrent?

A: Random fault 2310 during running (not startup) suggests: (1) intermittent mechanical jam or load spike (conveyor, mixer with lumpy material), (2) intermittent insulation failure on output cable (fault worsens with cable temperature), (3) loose output terminal connection causing arcing. Check mechanical load behavior, retest insulation when the cable is warm, and retorque all output terminal connections.

Q: Can I increase the overcurrent trip threshold on the ACS880 to prevent nuisance trips?

A: The instantaneous overcurrent trip (2310) threshold is fixed in firmware and is not user-adjustable — it’s a hardware protection. What you can adjust is the current limit (parameter 30.17) which limits how much current the drive will command. Lower current limit = less chance of tripping 2310 on demand spikes, but also less torque capability. Do not attempt to defeat 2310 protection — it exists to prevent IGBT destruction.

Q: How do I reset fault 2310 on the ACS880?

A: After addressing the root cause, press the RESET button on the ACS880 control panel, or send a reset command via fieldbus (bit 7 of the Control Word). The fault clears and the drive is ready to start. If the fault reappears immediately on start attempt, the root cause has not been resolved.